Maintaining transformers is more important now than ever before. Globally, demand for new transformers has lead times beyond three years. Unless there are enough spare transformers in inventory, it only makes sense to have a robust maintenance program. The three components that determine the lifespan of a transformer are: heat, moisture and oxygen.
The financial pressure of the industry has also impacted transformer manufacturers to reduce costs. Unlike transformers manufactured fifty years ago, new transformers are computer designed with minimal engineering margins. As a result, new transformers are designed with tight operating clearances. Any prolonged overloading or overheating conditions can dramatically reduce the lifespan of the transformer. Thus, it is important for transformer owners to monitor and test transformer oil on a regular basis. The testing frequency should be based on the oil status, voltage class and type of transformer. The question is, are you testing your transformer oil enough, and more importantly, what are you doing to prolong the life of your existing transformers?
Mineral oil is the lifeblood of a transformer and is by far the dominant fluid used in transformers. There are many reasons why mineral oil is used as an insulating fluid in transformers. One, it is an excellent dielectric medium for insulating the components within the transformer and two; it is a good heat transferring agent to dissipate the heat away from the windings to the tank walls and radiators. The radiators are designed to maximize the surface area to effectively cool the oil. The circulation of cool oil back through the windings is a continuous process. And third, it is still the cheapest fluid available for transformer applications.
But transformers will self-destruct over time. Heat and moisture combined with oxygen will cause a transformer to fail. If the transformer is properly maintained, the destruction process can take many years. But if the transformer is neglected, the transformer aging process can accelerate, and the lifespan can be quickly shortened. This is because of the insulation system within the transformer. The insulation system of a transformer consists of two components: oil and cellulose paper. Although the combination of oil and paper offers an excellent dielectric medium for the transformer, it is the interaction of the oil and the paper that will ultimately destroy the transformer. The hydrocarbons in the oil will form oxidation byproducts that decompose the cellulose insulation system. These byproducts will increase the moisture in the transformer as well as create an environment that will overheat the transformer. In time, the formation of these byproducts can cause the failure of the transformer.
Although it is important to test the oil in transformers, it is more important to know how to interpret the data from the results. No one test can be used independently to determine the oil condition.
Rather, all of the results should be reviewed simultaneously to give a full understanding about what is occurring in both the oil and the transformer. This will allow the customer to review the options and make a decision as to how to treat the oil. The IEEE Guide for the Reclamation of Insulating Oil and Criteria for Its Use (IEEE Std 637-2015)2 has the following group classifications for oil evaluation.
For oil that does not meet the recommended thresholds above, there are two options. One, the oil can be utilized in a lower voltage application, assuming it was utilized above a 69 kV application. Two, the oil can be reconditioned or reclaimed to meet the Group I classification requirements.
Although the acid test determines conditions under which sludge may form, it does not necessarily indicate that sludging conditions exist. The IFT test is a good indicator of the sludging characteristics of transformer oil because it correlates to the concentration of polar molecules in suspension and in the solution in the oil. Thus, the IFT test serves as an early warning to the beginning stages of deterioration.
It is important to not just consider these two tests as indicators as to whether or not oil treatment is necessary. Other oil quality results should be reviewed as well as dissolved gas analysis (DGA) results should also be considered.
The IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment, (C57.637-2015) has the following definitions5:
From a technical position, these are different processes to treat different problems. The first is chemical and the second is mechanical. However, from a practical position, it is necessary to remove all types of contaminants that destroy the insulation characteristics of a transformer. Since the purpose of a hot oil reclamation process is to prolong the life of the transformer, a hot oil reclamation process must have the ability to perform both chemical and mechanical oil treatment. Specifically, the reclamation process must have the ability to remove:
For on-site energized oil treatment, the Hot Oil Reclamation process begins mobilizing an oil processing rig to the site and connecting two sets of high-pressured hoses to the transformer. This will allow the oil to circulate the hot oil in a closed loop path. The oil needs to be pulled from the bottom of the transformer and return to the top.
There are six five components to the removal of harmful contaminants within the oil. The five components are as follows:
Heat
Heat is accomplished by literally heating the oil when it enters the rig. Heating the oil has will help dissolve the sludge layered in the transformer into a soluble form where it can be removed from the oil after entering the rig. This is why it is advantageous to perform the reclamation process on an energized transformer. The heat generated from the load will aid in transferring the moisture from the paper to the oil as well as dissolving the sludge buildup internal to the core and coil assembly. In addition, the mechanical vibration at 60 Hertz also aids in the circulation of the oil through the windings. This circulation is important to remove the sludge within the windings.
At approximately 180°F, the oil reaches the aniline point and becomes a solvent for it’s own decaying products within the oil. As the hot oil circulates through the transformer, it begins to dissolve the sludge that has built up within the core and coil as well as the radiators. The insoluble sludge that is carried out by the oil can be removed via filtering stages within the rig, while the soluble sludge can be removed via fullers earth, which will be explained later. The amount of sludge accumulated in the transformer will affect how many circulation passes are required. Transformers in poor condition may require as many as 20 passes to desludge the core and coil assembly. A pass is defined as the total gallons processed through the rig divided by the nameplate gallon rating. Thus, if a transformer has 2,000 gallons, and the rig circulates 40,000 gallons, then 20 passes were performed on the oil.
As the temperature increases in the transformer, moisture from the winding will transfer from the paper to the oil. As the oil circulates through the processing rig, the water is removed before re-entering the transformer. THIS PROCESS WILL NOT DRY OUT THE CELLULOSE INSULATION. 99.9% of the water in a transformer in the paper. Thermodynamically, it is impossible to transfer all the water from the paper to the oil for removal. Below you will find a graph that compares water absorption between paper and oil. Note the higher the temperature, the higher the water ppm is in the oil, and the lower the moisture content is in the paper. Remember, water has an affinity for paper, but when you introduce heat, it transfers the moisture into the oil. This is important because water in the paper will decompose the insulation integrity.
Fullers Earth
Fullers earth is a naturally mined adsorbent clay. Adsorption is the attraction of one substance to another substance. Fullers earth will adsorb water, acids, sludge, alcohols and other oil decaying products. Thus, as the oil passes through the fuller’s earth, the adsorption process will remove the dissolved acid, sludge and water from the oil. In addition, fullers earth will also adsorb microscopic particles and suspended carbon created from internal arcing. As a result, fullers earth improves both the power factor and the interfacial tension of the transformer oil while subsequently reducing the acid content. The continuous circulation of hot, dry clean oil through the energized transformer will also clean the transformer as it continues to dissolve sludge, oil decaying products and moisture from the insulation. Upon returning the “dirty” oil through the rig, the adsorption process will again remove the contaminants from the oil before returning to the transformer. This process is repeated until all incoming oil properties meet the minimum standards as outlined by the customer and the contractor. Attached is a graph that outlines the effectiveness of fuller earth in relationship to the acid content of the oil.
Vacuum Degassing-Dehydration
Before the oil returns to the transformer, it is important to have the oil pass through a vacuum degassing/dehydration column. Although there are several ways to achieve a high vacuum on the oil, the general idea is to maximize the surface area of the oil in order to remove dissolved moisture, oxygen and other gases. The vacuum degassing column will also remove volatile forms of acids, but fullers earth will be the primary method to extract acid from the oil. Since the circulation process will continue to remove moisture from the insulation, it is important to continuously operate the dehydration column so that wet oil does not return to the top of the transformer.
Inhibitor
Most transformers have an inhibitor additive to the oil. An inhibitor is important because it aids in the resistance of oxidation. On a sealed transformer, the benefits of inhibitor last for many years; however, as the inhibitor depletes, the rate of oxidation increases while the oil quality deteriorates. Most inhibitor utilized in transformer oil is 2,6 di-tertiary-butyl para-cresol (DBPC). Because of the reclamation process, an inhibitor is removed from the oil through the fullers’ earth bed and the vacuum degassing column. Thus, during the last pass, it is important to add DBPC to the oil as it is returning to the transformer for protection against oil oxidation.
Filter Stages
Because of the dangers of metallic particles and other foreign particles found inside the transformer, it is critical to have multiple filter houses throughout the rig to guard against particles from re-entering the transformer. Multiple filters throughout the rig ensure the protection of the transformer. Contaminants and particles in the oil not only degrade oil qualities such as dielectric and power factor, but contaminants such as iron particles also introduces the risk of failure. Thus, the very last step before the oil exits the rig is to pass through a 0.5 micron particle filter trap any remaining particles that have not been previously captured.
The advantage of the hot oil reclamation process is that, in most cases, it can be performed on energized transformers. Thus, the customer never has to take an outage and incur additional expenses of setting up a mobile transformer. In addition, the energized process helps to aid in the cleaning of the transformer. Typically, 230kV is considered the ceiling for performing hot oil reclamation on energized transformers. But not all transformers qualify. Performing a hot oil reclamation process on energized transformers is safe as long as:
The oil processing system must have the ability to eliminate bubble formation. Bubbles are stress points and have low dielectric strength. As a result, a bubble or a conglomerate of bubbles can cause arcing and or failure. Static charges can also develop when mineral oil flows through pipes and hoses so it is important to have the system grounded. In addition to the equipment, the crew must be very well trained to perform this service on energized transformers– both for the protection of the personnel and the equipment.
If a transformer is too small, or the voltage rating is above 230 kV, then it is recommended that the transformer be processed de-energized. Likewise, if the condition of the transformer oil is too poor because of high acids, high moisture, high dissolved gases, low dielectric or low interfacial tension, then the transformer cannot undergo a hot oil reclamation energized. Instead, the poor conditions force the transformer to be processed de-energized. Every time a transformer is de-energized and re-energized, there is a significant amount of electrical and mechanical stress on the transformer.
There is always the added risk that this stress could lead to failure of the transformer. This is especially true in older transformers. In addition, the added benefits of performing the reclamation process energized are lost when the transformer is reclaimed de-energized. Thus, it is advantageous to monitor and prevent the transformer from reaching a point where it cannot be reclaimed energized.
The goal is for the oil improve as visually shown in this picture