Key Gases and Fault Indicators in Transformer Oil

Hydrogen, ethylene, and acetylene can point to very different conditions inside a transformer. The useful question is which gases are changing together. Rising hydrogen with little change in the other gases can suggest a different condition than hydrogen rising alongside acetylene.

This guide explains what the gases on a dissolved gas analysis (DGA) report can indicate in a mineral oil-filled transformer.

What Each Gas Can Indicate

GasWhat it can indicate
Hydrogen (H₂)Often associated with partial discharge when it dominates the gas pattern. It can also form during arcing and other electrical activity, so the gases accompanying it matter.
Methane (CH₄)Can form during lower-temperature oil overheating. It can also accompany electrical discharge, particularly when hydrogen is present.
Ethane (C₂H₆)Often associated with lower-temperature thermal activity in oil. Compare it with methane and ethylene to see how the thermal gas pattern is changing.
Ethylene (C₂H₄)A prominent thermal fault indicator. When ethylene becomes more pronounced relative to methane and ethane, the pattern can suggest higher-temperature oil overheating.
Acetylene (C₂H₂)Can indicate arcing or other high-energy electrical activity. New or rising acetylene in a main-tank sample deserves review in the context of the transformer’s design and the sample location.
Carbon monoxide (CO)Can be produced as cellulose insulation ages or degrades under heat. A change in CO is assessed alongside CO₂, historical results, and other evidence of paper deterioration.
Carbon dioxide (CO₂)Can also be associated with cellulose aging and degradation. Its significance depends on the transformer’s history, design, and the rest of the gas pattern.
Oxygen (O₂) and nitrogen (N₂)Provide context about the oil preservation system and potential exposure to air. Nitrogen can also reflect a nitrogen blanket.

How Gas Patterns Help Distinguish Faults

Hydrogen is rising. Could it be partial discharge?

When hydrogen accounts for most of the increase and hydrocarbon gases remain comparatively low, partial discharge is one possibility. If acetylene is also rising, the pattern may point toward higher-energy electrical activity and warrants a different line of investigation.

Ethylene is increasing. Is the oil overheating?

A rise in methane and ethane can be consistent with lower-temperature oil heating. When ethylene becomes more prominent, the pattern can suggest higher-temperature thermal activity. The gas mix helps characterize the heating, while operating history and other findings help narrow down the source.

Acetylene appears. Where was the sample collected?

Acetylene in a main-tank sample calls for different interpretation than acetylene in an oil-filled load tap changer compartment where switching can generate arcing gases. Confirming the sample location and understanding the equipment design help put the result in context.

Carbon monoxide and carbon dioxide are changing. Is paper insulation involved?

Both gases can be associated with cellulose aging or thermal degradation. Review the unit’s prior results and other evidence before drawing a conclusion about the paper. Furan analysis can provide additional information when cellulose deterioration is suspected.

Get Help Interpreting Your DGA Results

A gas pattern can help identify the type of activity worth investigating. Previous samples help show whether the pattern is stable or changing, while loading, recent maintenance, oil processing, and sample location can explain why the latest results look different.

MVA provides transformer oil DGA testing and diagnostic review. If you’re following up on an unusual result, include previous reports and the sample location when you request a quote.